Modification History
Not Applicable
Unit Descriptor
Unit Descriptor |
1 ) 1 .1 ) Descriptor |
This unit covers inspection and testing to verify whether an electrical installation is safe and complies with all requirements. It encompasses working safely, visual inspections and mandatory, optional and functional test procedures, identifying non-compliance defects and mandatory reporting requirements. |
Application of the Unit
Application of the Unit |
4 ) |
This unit is intended to augment previously acquired competencies. It is suitable for employment-based programs under an approved contract of training. Note: |
Licensing/Regulatory Information
1 .2 ) License to practice |
The skills and knowledge described in this unit require a license to practice in the workplace subject to regulations for undertaking of electrical work. Practice in workplace and during training is also subject to regulations directly related to occupational health and safety and where applicable contracts of training such as apprenticeships. Note: |
Pre-Requisites
Prerequisite Unit (s ) |
2 ) |
2 .1 ) Competencies |
|
Granting competency in this unit shall be made only after competency in the following unit(s) has/have been confirmed. UEENEEE001B Apply OHS practices in the workplace UEENEEE002B Dismantle, assemble and fabricate electrotechnology components UEENEEE003B Solve problems in extra-low voltage single path circuits UEENEEE004B Solve problems in multiple path d.c. circuits UEENEEE005B Fix and secure equipment UEENEEE007B Use drawings, diagrams, schedules and manuals UEENEEE008B Lay wiring/cabling and terminate accessories for extra-low voltage circuits UEENEEE033B Document occupational hazards and risks in electrical work UEENEEG001B Solve problems in electromagnetic circuits UEENEEG002B Solve problems in single and three phase low voltage circuits UEENEEG003B Install wiring and accessories for low voltage circuits UEENEEG004B Install low voltage electrical apparatus and associated equipment UEENEEG007B Select and arrange equipment for general electrical installations UEENEEG008B Find and repair faults in electrical apparatus and circuits UEENEEG009B Develop and connect control circuits and elective units as required from Schedule 3 to a Strand Unit value of 6 Those holding an 'Unrestricted Electrician's Licence' or equivalent issued in an Australian State or Territory meet the requirements of this unit and its pre-requisite requirements. A 'licensed electrician' applying for an 'electrical contractors licence' may be required to undertake this unit to demonstrate their currency with verification of compliance requirements. In this case they are deemed to have met the prerequisites for this unit provided that:
For the full prerequisite chain details for this unit please refer to Table 2 in Volume 1, Part 2 |
Employability Skills Information
Employability Skills |
3 ) This unit contains Employability Skills The required outcomes described in this unit of competency contain applicable facets of Employability Skills. The Employability Skills Summary of the qualification in which this unit of competency is packaged will assist in identifying Employability Skill requirements. |
Elements and Performance Criteria Pre-Content
6 ) Elements describe the essential outcomes of a unit of competency |
Performance criteria describe the required performance needed to demonstrate achievement of the Element. Assessment of performance is to be consistent with the evidence guide. |
Elements and Performance Criteria
ELEMENT |
PERFORMANCE CRITERIA |
||
1 |
Prepare to inspect and test an electrical installation. |
1.1 |
OHS measures for the site are identified, obtained and understood. |
1.2 |
Established OHS risk control measures and procedures in preparation for the work are followed. |
||
1.3 |
Safety hazards, which have not previously been identified, are noted and established risk control measures are implemented. |
||
1.4 |
Documentation or deemed to comply standard on which installation is based is reviewed and understood. |
||
1.5 |
Appropriate personnel are consulted to ensure the work is coordinated effectively with others involved on the work site. |
||
1.6 |
Tools, equipment and testing devices needed to verify compliance are obtained in accordance with established procedures and checked for correct operation and safety. |
||
1.7 |
Preparatory work is checked to ensure no damage has occurred and complies with requirements. |
||
2 |
Visually inspect and conduct safety testing on the installation. |
2.1 |
OHS risk control measures and procedures for carrying out the work are followed. |
2.2 |
The need to test or measure live is determined in strict accordance with OHS requirements and when necessary conducted within established safety procedures. |
||
2.3 |
Circuits/machines/plant are checked as being isolated where necessary in strict accordance OHS requirements and procedures. |
||
2.4 |
Wiring is checked for suitability for the environments in which they are installed and suitably protected from damage or overheating. |
||
2.5 |
Cable conductor sizes are confirmed as meeting current-carrying capacity requirements and voltage-drop and fault-loop impedance limitations. |
||
2.6 |
Protection methods and devices are validated as meeting co-ordination requirements for overload and short-circuit protection. |
||
2.7 |
Switchgear and control gear is validated as being appropriately rated and meeting functional requirements. |
||
2.8 |
Evidence that electrical equipment complies with safety requirements is cited. |
||
2.9 |
Earthing system components are checked that they are correctly located and conductors correctly sized. |
||
2.10 |
Marking on switchboards are checked for accuracy and clarity and comply with requirements. |
||
2.11 |
Mandatory tests are conducted to verify that: earthing conductor resistance is sufficiently low; insulation resistance is sufficiently high; all polarities are correct; and circuit connections are correct. |
||
2.12 |
Testing is conducted to verify that: fault-loop impedance is sufficiently low and residual current devices operates as intended. |
||
3 |
Report inspection and test findings. |
3.1 |
OHS risk control work completion measures and procedures are followed. |
3.2 |
Work site is cleaned and made safe in accordance with established procedures. |
||
3.3 |
Non-compliance defects are identified and reported in accordance with established procedures. |
||
3.4 |
Recommendations for rectifying defects are made in accordance with established procedures. |
||
3.5 |
Mandatory documentation is completed in accordance with established procedures. |
Required Skills and Knowledge
REQUIRED SKILLS AND KNOWLEDGE |
||
7 ) This describes the essential skills and knowledge and their level, required for this unit. |
||
Evidence shall show that knowledge has been acquired of safe working practices and verifying compliance and functionality of general electrical installations. All knowledge and skills detailed in this unit should be contextualised to current industry practices and technologies. The extent of the essential knowledge and associated skills (EKAS) required is given in Volume 2 - Part 2.2 EKAS. It forms an integral part of this unit. |
||
2.7.5.1 |
Electrical installations, testing and verification |
Evidence Guide
EVIDENCE GUIDE |
|||
9 ) The evidence guide provides advice on assessment and must be read in conjunction with the Performance Criteria, Required Skills and Knowledge, the Range Statement and the Assessment Guidelines for this Training Package. The Evidence Guide forms an integral part of this unit. It must be used in conjunction with all parts of this unit and performed in accordance with the Assessment Guidelines of this Training Package. |
|||
Overview of Assessment |
9 .1 ) Longitudinal competency development approaches to assessment, such as Profiling, require data to be reliably gathered in a form that can be consistently interpreted over time. This approach is best utilised in Apprenticeship programs and reduces assessment intervention. It is the Industry's preferred model for apprenticeships. However, where summative (or final) assessment is used it is to include the application of the competency in the normal work environment or, at a minimum, the application of the competency in a realistically simulated work environment. It is recognised that, in some circumstances, assessment in part or full can occur outside the workplace. However, it must be in accordance with industry and regulatory policy. Methods chosen for a particular assessment will be influenced by various factors. These include the extent of the assessment, the most effective locations for the assessment activities to take place, access to physical resources, additional safety measures that may be required and the critical nature of the competencies being assessed. The critical safety nature of working with electricity, electrical equipment, gas or any other hazardous substance/material carries risk in deeming a person competent. Sources of evidence need to be 'rich' in nature to minimise error in judgment. Activities associated with normal every day work have a bearing on the decision as to how much and how detailed the data gathered will contribute to its 'richness'. Some skills are more critical to safety and operational requirements while the same skills may be more or less frequently practised. These points are raised for the assessors to consider when choosing an assessment method and developing assessment instruments. Sample assessment instruments are included for Assessors in the Assessment Guidelines of this Training Package. |
||
Critical aspects of evidence required to demonstrate competency in this unit |
9 .2 ) Before the critical aspects of evidence are considered all prerequisites shall be met. |
||
Evidence for competence in this unit shall be considered holistically. Each element and associated performance criteria shall be demonstrated on at least two occasions in accordance with the 'Assessment Guidelines - UEE07'. Evidence shall also comprise:
|
|||
|
|||
|
|||
|
|||
A |
Selecting correct tools and testing equipment. |
||
B |
Identifying visual non-compliance defects. |
||
C |
Using effective methods for conducting mandatory and optional tests. |
||
D |
Identifying non-compliance from test results. |
||
E |
Identifying causes of non-compliance. |
||
F |
Completing mandatory reporting. |
||
G |
Dealing with unplanned events by drawing on essential knowledge and skills to provide appropriate solutions incorporated in the holistic assessment with the above listed items. |
||
Context of and specific resources for assessment |
9 .3 ) This unit should be assessed as it relates to normal work practice using procedures, information and resources typical of a workplace. This should include:
These should be part of the formal learning/assessment environment. Note: Where simulation is considered a suitable strategy for assessment, conditions must be authentic and as far as possible reproduce and replicate the workplace and be consistent with the approved industry simulation policy. |
||
The resources used for assessment should reflect current industry practices in relation to verifying compliance and functionality of general electrical installations. |
|||
Method of assessment |
9 .4 ) This unit shall be assessed by methods given in Volume 1, Part 3 'Assessment Guidelines'. Note: |
||
Concurrent assessment and relationship with other units |
9 .5 ) |
||
There are no concurrent assessment recommendations for this unit. |
|||
The critical aspects of occupational health and safety covered in unit UEENEEE001B and other discipline specific occupational health and safety units shall be incorporated in relation to this unit.. |
Range Statement
RANGE STATEMENT |
8 ) This relates to the unit as a whole providing the range of contexts and conditions to which the performance criteria apply. It allows for different work environments and situations that will affect performance. |
This unit shall be demonstrated in relation to verifying compliance and functionality of at least two electrical installations comprising of a main switchboard; at least supplying lighting, one circuit supplying socket outlets and one circuit supplying a fixed appliance. One of the installations shall include a distribution board additional to the main switchboard and a circuit supplying a three-phase load. |
Generic terms used throughout this Vocational Standard shall be regarded as part of the Range Statement in which competency is demonstrated. The definition of these and other terms that apply are given in Volume 2, Part 2.1. |
Unit Sector(s)
Not Applicable
Competency Field
2 .2 ) Literacy and numeracy skills Participants are best equipped to achieve competency in this unit if they have reading, writing and numeracy skills indicated by the following scales. Description of each scale is given in Volume 2, Part 3 'Literacy and Numeracy' |
|||||
Reading |
4 |
Writing |
4 |
Numeracy |
4 |
Custom Content Section
Competency Field |
5 ) |
Electrical |